 ====== MitsuRunner introduction ====== ====== MitsuRunner introduction ======
  
-Software for ESP8266 or ESP32 based device designed to prevent Mitsubishi Electric heatpumps to do too short heating runs and de-frosting the outdoor unit every 30 minutes or so. This .yaml file is designed for https://ESPhome.io, which is needed to generate, compile and update sources. Please follow the information on their site how to set-up environments.+Software for ESP8266 or ESP32 based devices designed to prevent Mitsubishi Electric heatpumps from doing too short heating runs and de-frosting the outdoor unit every 30 minutes or so. This .yaml file is designed for https://ESPhome.io, which is needed to generate, compile and update sources. Please follow the information on their site how to set-up environments.
  
-Many Finns suffer from poor design of Mitsubishi heat pumps. In normal winter at -15 c degrees especially MSZ-LN series does de-frost every 30/40 minutes even when there is practically no frost in the outdoor unit, ie. no need to defrost. Frequent de-frost leads to poor heat production and most likely very poor effiency ("COP") compared to a unit where defrost happens only once every 2-3 hours in the same conditions.+Many Finns suffer from the poor design of Mitsubishi heat pumps. In normal winter at -15 c degrees especially MSZ-LN series de-frosts every 30/40 minutes even when there is practically no frost in the outdoor unit, ie. no need to defrost. Frequent de-frosting leads to poor heat production and most likely very poor effiency ("COP") compared to a unit where defrost happens only once every 2-3 hours under the same conditions.
  
 ===== Background ===== ===== Background =====
  
-This software started from a topic in lampopumput.info forum: https://lampopumput.info/foorumi/threads/msz-ln-sulatushuijaus.31223/ +This software started from a topic in the lampopumput.info forum: https://lampopumput.info/foorumi/threads/msz-ln-sulatushuijaus.31223/ 
  
-The design of these Mitsubishi MZN-LN25/35 etc. heatpumps is poor both in software and in mechanics. **The software in the unit does not suit the Finnish climate - and most probably not any climate where the pump needs to be used for heating and the temperature goes below -5 degrees.** The pump heats mainly with short cycles (under 60 minutes) and tries to melt ice from outdoor unit's heat exhanger even when there is no ice. This is a waste of energy and makes heating inefficient. +The design of these Mitsubishi MZN-LN25/35 etc. heatpumps is poor both in software and mechanically. **The software in the unit does not suit the Finnish climate - and most probably not any climate where the pump needs to be used for heating and the temperature goes below -5 degrees.** The pump heats mainly with short cycles (under 60 minutes) and tries to melt ice from outdoor unit's heat exhanger even when there is no ice. This is a waste of energy and makes heating inefficient. 
  
-This is due to poor "fuzzy logic" algorithm which: +This is due to the poor "fuzzy logic" algorithm which: 
   * Instead of using temperature sensors it tries to predict de-frost need from previous cycles.   * Instead of using temperature sensors it tries to predict de-frost need from previous cycles.
   * The mechanical side of the probems are related to the defrost temperature sensor. It is used to detect when the ice has melted from the outdoor heat exhanger. The defrost temperature sensor is installed poorly so it touches non-waterproof insulation material which gets wet from melting water/condensation and then freezes. **The frozen defrost sensor does not measure correct value needed for the "fuzzy logic".** Thus it starts to affect the device's "fuzzy logic" which starts to think that heating has been too long as outdoor heat exhanger is too icy and thus starts to decrease duration of heating... and this leads to a situation where the pump does not heat much but tries to melt the outdoor unit's heat exhanger often. Basically wasting energy by melting really often means it heats the outside air by taking heat from inside.    * The mechanical side of the probems are related to the defrost temperature sensor. It is used to detect when the ice has melted from the outdoor heat exhanger. The defrost temperature sensor is installed poorly so it touches non-waterproof insulation material which gets wet from melting water/condensation and then freezes. **The frozen defrost sensor does not measure correct value needed for the "fuzzy logic".** Thus it starts to affect the device's "fuzzy logic" which starts to think that heating has been too long as outdoor heat exhanger is too icy and thus starts to decrease duration of heating... and this leads to a situation where the pump does not heat much but tries to melt the outdoor unit's heat exhanger often. Basically wasting energy by melting really often means it heats the outside air by taking heat from inside. 